| 1. Specification of AD110 small and economical type 1PH, 220V input, 3 phase output VFD | |||||
| Model | AD110-2S0.1G | AD110-2S0.2G | AD110-2S0.4G | AD110-2S0.75G | |
| Output | Rated output power | 100w | 200w | 400w | 750w |
| Rated output current | 0.8A | 1.0A | 2.0A | 3.8A | |
| Overload tolerance | 150% rated current for 60s | ||||
| Max output voltage | 3 phase 240V | ||||
| Input | Rated input voltage | single phase 200- 240VAC | |||
| Voltage Tolerance | Single phase 180 -250VAC | ||||
| Frequency accurace | ±5% | ||||
| Power capacity | 0.8 KVA | ||||
| Cooling Method | Nature Air- Cooling | ||||
| Consumption wattage | 15w -25w | ||||


| Using conditions of AD110 VFD | ||
| Operation conditions | Ambient Temperature | -10℃ to 50℃ |
| Relative Humidity | < 85% ( no condensation Allowed) | |
| Atmosphere pressure | 86 to 105Kpa | |
| Installation Site Altitude | <1000m | |
| Vibration | <20Hz | |
| Storage Transportation conditions | Air Temperature | -10℃ to 60℃ |
| Ambient Humidity | < 90% ( no condensation allowed) | |
| Vibration | <20Hz | |
| Pollution Degree | 2 Class: good for factory type environment | |


7. Summary of parameters settings of AD110 VFDs
| Parameter | explanation | settings | Factory setting |
| P00 | Frequency reference | 0 ~ 99Hz ( unit: 0.5Hz) | |
| P01 | source of frequency command |
0: Interface keypad control 1: Interface Potentiometer 2:exterior potentiometer 3:Rs485 |
1 |
| P02 | Run/stop of operation command |
0:interface keypad control 1:Rs485 2:Forward running while power input 3:Reverse Running while power input 4:Exterior input |
0 |
| P03 | Stop method | 0: Cost stop 1: Ramp stop 2: Brake stop | 1 |
| P04 | Max output frequency | 0 ~ 100Hz | 65Hz |
| P05 | Min Output frequency | 0 ~ 100Hz | 5Hz |
| P06 | Acceleration time | 0 ~ 250Hz/sec | 50Hz/sec |
| P07 | Deceleration time | 0 ~ 250Hz/sec | 50Hz/sec |
| P08 | Brake lead time | 0 ~3 sec | 0.3 sec |
| P09 | Brake value | 0~ 60% | 20%% |
| P10 | 3Hz VF value | 0 ~ 50% | 4% |
| P11 | 50Hz | 0 ~ 99% | 98% |
| P12 | Rs485 frame ASCII | 0:7E1 1:7O1 2:8N2 3:8E1 4:8O1 | 20%% |
| P13 | Rs485 protocol |
0:4800 1:19200 2:9600 3: 38400 |
1 |
| P14 | Communication address | 1 ~ 255 | 1 |
| P15 | MI mode selection |
0: MI1 FWD/stop, MI2 REV/STop 1: MI1 RUN/stop, MI2 FWD/REV 2:MI1 RUN/Stop, MI2 Multiple-stop speed |
0 |
| P16 | MO mode selection |
0: Running indication 1: Max output frequency arrive 2: Fault indication |
0 |
| P17 | Multiple -step speed command | P04~p05 | 50 |
| P18 | Frequency arrive frequency | P04~p05 | 50 |
| P19 | overload tolerance | 1 ~ 100% | 50% |
| P20 | Temperature tolerance | 1℃ ~80℃ | 80℃ |
| P21 | Speed proportion | 0.25 ~100 | 1 |